What this guide covers
New Brunswick and Nova Scotia both follow the National Building Code 2020. It has two sets of rules for stairs and railings:
- Part 9: houses and small buildings, up to 3 storeys and 600 m².
- Part 3: larger buildings and public places like schools, stores and big condos.
Part 9: houses and small buildings (Section 9.8)
Most residential stairs we build fall under Section 9.8. The code sorts stairs into two types:
- Private stairs serve a single dwelling unit, or a garage that serves one. Example: the stair inside a house or up to its deck.
- Public stairs are everything else. Example: a shared exterior stair to the balconies of a 4 unit building.
Step dimensions
| Item | Private stair | Public stair |
|---|---|---|
| Rise per step | 125 to 200 mm (5" to 7 7/8") | 125 to 180 mm (5" to 7") |
| Run per step | 255 to 355 mm (10" to 14") | 280 mm (11") min |
| Tread depth | 235 to 355 mm (9 1/4" to 14") | See code |
| Rise difference, adjacent steps | 5 mm max | 5 mm max |
| Rise difference, tallest vs shortest in a flight | 10 mm max | 10 mm max |
| Nosing bevel or radius | 6 to 14 mm | 6 to 14 mm |
The 5 mm tolerance includes the top and bottom steps, so finished floor thickness has to be in your rise calculation. This is the most common reason a stair fails inspection.
Width, headroom and landings
| Item | Private stair | Public stair |
|---|---|---|
| Minimum width | 860 mm (33 7/8") | 900 mm (35 7/16") |
| Minimum headroom | 1950 mm (6' 4 3/4") | 2050 mm (6' 8 3/4") |
| Landing width | same as stair | same as stair |
| Landing depth | stair width or 1100 mm, whichever is less | See code |
Headroom is measured straight up from a line through the tread nosings. A landing is needed at the top and bottom of every flight. Two exceptions: an interior stair where the door at the top swings away from the stair, and an exterior stair at a secondary entrance with 3 risers or fewer.
Winders: only one set per flight, either two at 45° or three at 30°, so 90° of turn at most.
Handrails
- At least one handrail is required. Stairs 1100 mm wide or more need one on both sides.
- Not required in a single dwelling for interior stairs with 2 risers or fewer, or exterior stairs with 3 risers or fewer.
- Height: 865 to 965 mm (34" to 38") above the nosing line. Where the handrail is the top of a guard, it can go up to 1070 mm.
- Clearance from the wall or anything behind it: 50 mm min.
- Continuously graspable along the full length, except inside a single dwelling. Newel posts can't interrupt it.
- Extensions: at least one handrail runs 300 mm level past the top and bottom of each flight. Not required for stairs serving one dwelling unit, or a house with a secondary suite.
- Supports every 1.2 m max, with the end supports within 300 mm of each end.
- Loads: 0.9 kN point load in any direction. Handrails outside dwelling units also need 0.7 kN/m.
Guards
A guard is required wherever the drop is 600 mm (24") or more.
| Location | Minimum height |
|---|---|
| Inside a dwelling unit | 900 mm (35 7/16") |
| Exterior deck or balcony, drop under 1.8 m | 900 mm |
| Exterior deck or balcony, drop 1.8 m or more | 1070 mm (42") |
| On a stair flight | 900 mm above the nosing line |
| All other guards (common areas, public stairs) | 1070 mm |
- Openings: a 100 mm (4") sphere must not pass through anywhere in the guard.
- Climbing: no rails, ledges or openings that make it easy to climb between 140 mm and 900 mm above the floor. Inside a dwelling this only applies where the drop is over 4.2 m, which is why horizontal cable guards are allowed below that height.
- Glass: must be safety glass (tempered or laminated).
Part 3: larger and public buildings (Section 3.4)
In a Part 3 building, most stairs are exit stairs, the protected routes people use to get out in a fire. The rules are stricter, and the stair and its guards must be designed and sealed by an engineer. For steel, the welding has to be done by a CWB certified shop (CSA W47.1).
Step dimensions
| Item | Exit stair |
|---|---|
| Rise per step | 125 to 180 mm (5" to 7") |
| Run per step | 280 to 355 mm (11" to 14") |
| Rise difference, adjacent steps | 5 mm max |
| Rise difference, tallest vs shortest in a flight | 10 mm max |
| Rise and run between flights | must not change noticeably from one flight to the next |
Width, headroom and landings
- Width: 1100 mm (43 5/16") minimum for exit stairs. The required width also grows with the number of people the stair serves, at 8 mm per person.
- Headroom: 2050 mm (6' 8 3/4") minimum.
- Landings: at least as wide as the stair, and as deep as the stair is wide. Required at the top and bottom of each flight.
- Height of one flight: 3.7 m max between landings.
Handrails
- Required on both sides of every exit stair.
- Every part of the required width must be within 750 mm of a handrail. In practice, a stair wider than about 1650 mm needs an intermediate handrail.
- Height: 865 to 965 mm above the nosing line.
- Continuously graspable, with no breaks at newels or landings.
- Extensions: 300 mm level past the top and bottom of each flight.
- Accessibility rules also apply to most Part 3 buildings and can add handrail and contrast requirements: the Barrier-Free Design Building Code in NB, and Nova Scotia's own code amendments in NS.
Guards
- Every exit stair needs a wall or a guard on each side.
- On the stair flight: 920 mm (36 1/4") min, measured above the nosing line.
- At landings, balconies and floors: 1070 mm (42") min.
- Openings: 100 mm sphere rule, same as Part 9.
- Climbing: no climbable elements between 140 mm and 900 mm, except in industrial areas.
Quick comparison
| Item | Part 9 private | Part 9 public | Part 3 exit stair |
|---|---|---|---|
| Rise | 125 to 200 mm | 125 to 180 mm | 125 to 180 mm |
| Run | 255 to 355 mm | 280 mm min | 280 to 355 mm |
| Min width | 860 mm | 900 mm | 1100 mm |
| Min headroom | 1950 mm | 2050 mm | 2050 mm |
| Handrails | 1 side (2 if 1100 mm wide or more) | 1 side (2 if 1100 mm wide or more) | both sides |
| Handrail height | 865 to 965 mm | 865 to 965 mm | 865 to 965 mm |
| Handrail extension | not required | 300 mm | 300 mm |
| Guard on stair | 900 mm | 900 mm | 920 mm |
| Guard at landing or deck | 900 mm, or 1070 mm over 1.8 m drop | 1070 mm | 1070 mm |
Before you build
This guide is a summary to help you plan. The building code itself, your local building official and your engineer have the final word.